Micropack Rectifiers 5g Network Equipment Eltek Rectifier Module 241120.200

Products

Micropack Rectifiers 5g Network Equipment Eltek Rectifier Module 241120.200

Micropack Rectifiers 5g Network Equipment Eltek Rectifier Module 241120.200

24V 240W Micropack Rectifiers Low Voltage Eltek Rectifier Module 241120.200 Description Compact, full-featured DIN- rail

Send your inquiry

DESCRIPTION

Basic Info.
Model NO. 241120.200
Power Factor 0.98 (@ 55-100 % Load)
Thd (@ 230 VAC) <5% (@ 50-100 % Load)
Dimensions 39.0X88.5X149mm
Transport Package Carton Box
Specification Brand New
Trademark Eltek
Origin Wuhan
Production Capacity 1000 Sets/Month
Product Description

24V 240W Micropack Rectifiers Low Voltage Eltek Rectifier Module 241120.200

Description

Compact, full-featured DIN- rail power system

The Micropack System is convection cooled, designed for less power hungry applications, but still with system functionality options to match any requirements. Use as stand alone or in a flexible off the shelf configurable system.

The Micropack Power System extends your network one step further. With load ranges typically between 120W and 1000W, and in 12, 24 and 48V options, the system is perfect for a great variety of applications.

INDUSTRY APPLICATIONS

Telecom

·LTE/ femto cells

·Small base stations / repeaters

·Fixed & mobile broadband

·FTTx

Power utilities

·Control & protection

·Scada

·Communication

Railway infrastructure

·Control & protection

·Signaling

Various other applications in demanding industries like Marine, Oil & Gas, process etc.

KEY FEATURES

Convection cooled - inaudible

Accepts 85 - 300 V AC/ DC input

12, 24-30, 48 V DC output versions

NiCad support for 12 and 24V DC

Quick-trip pulse to help open load MCB

Pot-meter voltage adjustment for standalone

Module alarm relay contact for basic monitoring without controller

Active current sharing

Comprehensive monitoring and control when used with controller:

  • Remote/ local connection through Ethernet
  • Webpages and SNMP support
  • Monitoring of rectifier temperature, input voltage and output current

Modular approach in DIN-rail mountable back planes

Off-the-shelf delivery

Specifications

Model24V / 240W
Part number241120.200
INPUT DATA
Voltage range85 - 300 V AC/ DC 1)
Voltage range (nominal)185 - 275 V AC/ DC 1)
Frequency0 - 66 Hz 1)
Maximum current, 230V input / overall (boost)1.2 A / 2.0 A
Maximum earth leakage current2.0 mA (@ 250V AC/ 50Hz)
Power Factor0.98 (@ 55 - 100 % load)
THD (@ 230 VAC)< 5 % (@ 50 - 100 % load)
ProtectionVaristor for transient protection, fuse in both lines (2x 2.0 A), shutdown above 300 V AC/ DC
OUTPUT DATA
Default voltage27.2 VDC
Voltage range21.5 - 36 V DC
Voltage range without controller21.5 - 30 V DC
# Pb cell supported (1.8 - 2.4 V DC/ cell)12 - 15
# NiCad cell supported (1.05 - 1.65 V DC/ cell)20 - 22 2)
Max power, nominal / 60s boost240 W / 315 W
Max current, @12/ 24/ 48V DC / boost / QT 3)10 A / 15 A / 55 A
Current sharing±5% of maximum current from 10 to 100% load
Static voltage regulation ±0.5% from 10% to 100% load and nominal input
Dynamic voltage regulation± 5 % < 10ms, load step 10% to 90% or opposite at nominal output voltage
Hold-up time, default voltage and full power20 ms, VOUT > 21.5 VDC
Rippel and noise, 30 MHz b.w. / psophometric< 200 mV PP / 5 mV RMS
ProtectionOvervoltage shutdown, short circuit proof, high temperature, hot plug -in inrush current limiting, fuse
OTHER SPECIFICATIONS
Efficiency @ nominal input/ output, peak/ range93.0% / >92%, 50-100% load
Isolation3.0 kVAC - input and output, 1.5 kV AC - input earth, 0.5 kV DC - output earth
Alarms: Red LED 'onLow mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings: Yellow LED 'on'Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (module running): Green LED 'on'
Alarm output (isolated)NO (+positive terminal), COM (-negative terminal). 60 V / 100 mA max
MTBF (Telcordia SR-332 Issue I method III (a))>480 000h (@T AMBIENT= 25°C)
Operating temperature (5 - 95% RH non-cond.) Output power de-rates above temp / to

-40 to +60°C [-40 to +142°F]

+45°C / 80W @ +60°C

Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight39.0 x 88.5 x 149mm [1.54 x 3.48 x 5.87"] / 0.5 kg [1.1 lbs]
DESIGN STANDARDS
Electrical safetyUL 60950 -1, EN 60950 -1, CSA 22.2
EMC

ETSI EN 300 386 V.1.3.2

EN 61000-6-1 / -2 / -3 / -4 / -5 4)

Mains HarmonicsEN 61000 -3-2
Environment

ETSI EN300 019: 2 -1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)

ETSI EN 300 132-2

2002/ 95/ EC (RoHS) & 2002/ 96/ EC (WEEE)

Marine compliance

(EMC class B with AC filter)

DnV Rules for Classification of Ships, High Speed & Light Craft and DnV Offshore Standards

DC support for 241120.200 with primary FW 404088.009 (from HW revision 1.2) and 241120.100 from HW revision 2

11/ 22 cells with max boost voltage 1.636 V DC/ cell

Quick-Trip function, if V OUT = 5 VDC a 35 ms current pulse is generated to help trip fuse/ MCB on short circuited branch

Only 12V and 24V

Compack controller

1Rectifier moduleEmerson /VertivR48-1800A
2Rectifier moduleEmerson /VertivR48-2000A3
3Rectifier moduleEmerson /VertivR48-2900U
4Rectifier moduleEmerson /VertivR48-3000e3
5Rectifier moduleEmerson /VertivR48-3500e
6Rectifier moduleEmerson /VertivR48-5800A
7Rectifier moduleHuawiR4850N1
8Rectifier moduleHuawiR4850G1
9Rectifier moduleEltekFlatpack2 48/2000 HE241115.105
10Rectifier moduleEltekFlatpack2 48/1000 HE241122.105
11Rectifier moduleEltekFlatpack2 48/3000 HE241119.105
12Rectifier moduleEatonAPR24-3G